Profinet pin 2 configuration for UA on sensor hub up to GSDML 2.3x for TIA and Simatic Manager

1. Introduction

In order to operate our IO-Link sensor-actuator hubs without an external power supply with outputs on our IO-Link masters, it may be necessary to provide an actuator supply via pin 2.

These instructions are intended to explain the configuration for our IO-Link masters with Profinet up to GSDML <= 2.3x.
For the newer GSDML from version 2.4x and following, please use the corresponding document.

2. Recognize diagnostic messages

IO-Link sensor hub is connected to port and SF error is present on the IO-Link master

Diagnostics for the IO-Link port is available via channel diagnostics

3. Configuration in TIA

Configuration in the TIA Portal using the GSDML

3.1. Actuator voltage pin 2 Configure

The "Outputs pin 2" module must be dragged from the hardware catalog to a free slot in the hardware configuration and then assigned to an output address.





In addition, the respective port direction for the individual pins/ports must be set in the module parameters of the head module (slot 1).
In our case, port 0, pin 2.

3.2. Switch actuator voltage pin 2

The corresponding ports can now be switched on via the "Outputs Pin2" byte.


To do this, either activate the corresponding output byte as required in the running program or activate it as a test via the watch table.


Pin 2 should be switched immediately (orange LED on the IO-Link master port / Pin2) and the diagnostic message should disappear.

4. Configuration in the Simatic Manager

Configuration in the Simatic Manager using the GSDML

4.1. Actuator voltage pin 2 Configure

The "Outputs pin 2" module must be dragged from the hardware catalog to a free slot in the hardware configuration and then assigned to an output address.


In addition, the respective port direction for the individual pins/ports must be set in the module parameters of the head module (slot 1).
In our case, port 0, pin 2.


4.2. Switch actuator voltage pin 2

The corresponding ports can now be switched on via the "Outputs Pin2" byte.


To do this, either activate the corresponding output byte as required in the running program or activate it as a test via the watch table.

Pin 2 should be switched immediately (orange LED on the IO-Link master port / Pin2) and the diagnostic message should disappear.

5. Configuration successful

In this example, port 0 / pin 2 should now be active, the SF LED should be off and the port 0 LED for pin 2 should light up

6. FAQ - Error persists

Have you switched "Pin 2" and the diagnosis remains active?

  • Is the actuator voltage present at the master?
  • Was a 4-wire cable used between the master and device?
  • Can a cable break be ruled out?
Energy consumption labeling
Energy consumption labeling

EPREL - European Product Database for Energy Labeling

¿Tiene alguna pregunta o sugerencia? Estamos a su disposición.

Para todas las cuestiones relacionadas con temas comerciales, como presupuestos, pedidos o plazos de entrega, nuestro departamento de ventas internas estará encantado de atenderle.


Servicio Técnico
Para solicitudes técnicas relacionadas a productos o soluciones, por favor contacta a nuestro equipo de Servicio Técnico: [email protected]


Ventas Internas
Para cualquier duda referente a temas comerciales como cotizaciones o tiempos de entrega, nuestro equipo de ventas internas te atenderá con gusto: [email protected]


Balluff de México

Anillo Vial II Fray Junípero Serra
No. 4416
Colonia La Vista Residencial.
Querétaro, Qro. CP 76146

Muestra gratuita de producto

Para añadir un producto de muestra gratuita a la cesta tendremos que eliminar todos los productos normales de la cesta. ¿Está seguro de que desea continuar?