ACTIVATE/DEACTIVATE PROFINET MASTER IN TIA PORTAL
1. Introduction
In some cases is possible we want to deactivate a master Profinet. For example, in a machine with interchangeable tools, if in every tool there is a master, to avoid the no master presence error in Tia Portal, could be interesting this feature.
2. Scope
This FB works for Siemens S7-1500 and S7-1200. Demonstrations has been made with BNI00HL (FW 1.3.0) with CPU 1511F-1 PN (FW V2.0).
3. Tia Portal
The Tia Portal FB to activate or deactivate a Profinet device is “D_ACT_DP”

“D_ACT_DP” is an asynchronous instruction.
The parameters are the following:
- REQ: Job trigger
- MODE:
- 0: Request current status of the master
- 1: Activate master
- 2: Deactivate master
- LADDR: Hw ID of the master
- RET_VAL: Return answer from FB, or if an error occurs while the instruction is being executed, the return value contains an error code
- BUSY:
- 1: The job is still active
- 0: The job was ended
Parameter RET_VAL:
|
Error code (W#16#...) |
Explanation
|
|
0000 |
Job completed without error. |
|
0001 |
The DP slave/PROFINET IO device is active (this error code is possible only with MODE=0). |
|
0002 |
The DP slave/PROFINET IO device is deactivated (this error code is possible only with MODE = 0. |
|
7000 |
First call with REQ= 0: The job specified with LADDR is not active; BUSY has the value "0". |
|
7001 |
First call with REQ= 1. The job specified with LADDR was triggered. BUSY has the value “1”. |
|
7002 |
Intermediate call (REQ irrelevant). The activated job is still active; BUSY has the value "1”. |
|
8090 |
• You have not configured a module with the address specified in LADDR. • For firmware versions < V2.9: You operate your CPU as I-slave / I-device and you have specified an address of this I-slave/I-device in LADDR. Note: As of firmware version V2.9 of the S7-1500 CPU, it is possible to switch the I-device functionality on or off locally in the program of the I-device CPU with the “D_ACT_DP” instruction. |
|
8092 |
The deactivation of the currently addressed DP slave/PROFINET IO device (MODE=2) cannot be canceled by being activated (MODE=1). Activate the component at a later time. |
|
8093 |
The address specified in LADDR does not belong to any DP slave/PROFINET IO device that can be activated or deactivated or the MODE parameter is unknown. |
|
8094 |
You have attempted to activate a device which is potential partner for a tool change port. However, another device is already activated on this tool change port at this time. The activated device will remain activated. |
|
80A0 |
Error during the communication between the CPU and the IO controller |
|
80A3 |
The DP master/PROFINET IO controller concerned does not support this function. |
|
80A4 |
The CPU does not support this function for external DP masters/PROFINET IO controller. |
|
80A7 |
A timeout occurred during activation: The remote device is unreachable or you have set the configuration time for central and distributed I/O too short. The status of the remote device is "activated", but it is not reachable. It therefore does not supply I/O data |
|
80AA |
The DP Slave/PROFINET I/O device was successfully activated and supplies I/O data, but is not error-free: The DP slave / PROFINET IO device has missing or incorrect submodules. |
|
80AB |
The DP Slave/PROFINET I/O device was successfully activated and supplies I/O data, but is not error-free: The DP slave/PROFINET IO device has at least one submodule with a parameter assignment error (Application Ready Pending). |
|
80AC |
The DP Slave/PROFINET I/O device was successfully activated and supplies I/O data, but is not error-free: The DP slave/PROFINET I/O device has at least one submodule with a maintenance diagnostics (Own State Maintenance Required, Maintenance Demanded or Maintenance Error). |
|
80C3 |
• Temporary resource error: The CPU is currently processing the maximum possible activation and deactivation jobs (8). • The CPU is busy receiving a modified configuration. Currently you can not activate/deactivate DP slaves/PROFINET IO devices. |
How is possible to identify HW ID?

Disclaimer
Les informations techniques fournies ici gratuitement en réponse à votre demande sont basées sur les connaissances dont dispose BALLUFF et visent à vous accompagner au mieux dans votre question technique ou votre application et à proposer des pistes de solution.
Étant donné que ces informations techniques sont fournies gratuitement, la responsabilité de BALLUFF pour les défauts matériels et juridiques est exclue, sauf en cas de faute intentionnelle ou de négligence grave de la part de BALLUFF, ou en cas de dol. À cet égard, BALLUFF n’est responsable des dommages résultant de défauts des informations techniques ou de la violation d’autres obligations contractuelles ou extracontractuelles qu’en cas de faute intentionnelle ou de négligence grave. La limitation de responsabilité ci-dessus ne s’applique pas en cas de dol, d’atteinte à la vie, à l’intégrité physique ou à la santé, en cas de prise en charge d’une garantie, ainsi qu’en matière de responsabilité selon la loi sur la responsabilité du fait des produits. Toute responsabilité supplémentaire de BALLUFF est exclue.