(X)-LDPS sample project Commissioning
1. Project integration in TIA (hardware configuration)
The module, the software and the XML file are available in the download area of the (X-)LDPS:

The finished project can be opened in the TIA Portal software:

The project and the magnet track software are available in the folder:

As soon as the project is loaded, it can be swapped to the corresponding PLC:

Attention:
When replacing the PLC, please reactivate the checkbox for connection mechanisms, otherwise the Magnettrack software will not be able to access the PLC!

2. Settings in BTL and DB702
Please check that the BTL is operated in FFM mode and that the module access point/start address of the inputs is the same as in the DB702:

DB702 in the Sensor tab:

3. Settings in the DB700 using the instructions
To find the correct settings in the DB700, open the following instructions:

In the DB700, the following values from the table must be adjusted depending on the application:

To be entered here in the DB700:

4. Application in operation
Once the previous steps have been completed, the Magnettrack software can be started and the IP address of the PLC can be accessed:
Check IP addresses checks the access, next the data block connection can be checked with Check databases.
The connection is saved with Save .

A complete initialization must now be carried out:

Please confirm with Yes :

Done: