IO-Link Master Entry Line Integration with Rockwell without ADD-ON INSTRUCTION

1. Introduction

In this application we will integrate the new IO-Link Master Entry Line (BNI00HP) with a Rockwell PLC via Ethernet/IP without Add-On Instruction.

2. Configuring a Port on IO-Link

The bits refer to the pins of each port, that is, bit 0 – pin 4 and bit 1 – pin 2, bit 2 – pin 4 and bit 3 – pin 2 and so on...

If I want its port 0 to be IO-Link, I'll throw the "0" bit (pin 4) of 0 byte to 1

If I want its port 0 and its port 4 to be IO-Link, I'm going to throw the "0" bit (pin 4) of byte 0 and byte 1 to 1.

3. IO-Link configurations on ports

The example above would be for the IO-Link configurations on port 1, where it is separated from byte 2 to byte 25, as mapped:

If we were to configure port 3, for example, we would use byte 50 to byte 73

4. Process Data Input

To visualize the output state of the discrete sensor, we must enter the input data and track the bytes from 0 to 7.

In these 8 bytes (0 to 7), we will have the information below:

Plugging a sensor, for example, into port 6, we will see bits 4 and 5 of byte 1

Inside Rockwell, we would have the following visualization:

-Sensor Disabled (Pin 2 Enabled ):

-Sensor actuated (Pin 4 Enabled)

The data of the IO-Link ports is separated from byte 8, in this case it will depend on which port we would like to view and which information.

The information would be in the following structure:

5. Process Data Output

To view the output information, we track bytes from 0 to 5. In these 6 bytes, we will have the information below:

If we want to force an output on port 1, we'll see bits 2 and 3 of my byte 0.

Since in this master pin 2 cannot be configured as output, we will only look at bit 2

Inside Rockwell, we will see as follows

The data from the IO-Link ports is separated from byte 6, in this case it will depend on which port we would like to view.

Energy consumption labeling
Energy consumption labeling

EPREL - European Product Database for Energy Labeling

Máte nejaké otázky alebo návrhy? Radi vám pomôžeme.

Môžete nás kontaktovať niekoľkými spôsobmi. Tešíme sa, že vám môžeme pomôcť.

Kontaktujte nás priamo telefonicky: +421 2 672 000 61


Balluff Slovakia s.r.o.

Balluff Slovakia s.r.o.
Mlynské nivy 73,
Bratislava - mestská časť
Ružinov 821 05

Spojte sa s nami:
[email protected]

Bezplatná vzorka produktu

Aby sme mohli do košíka pridať bezplatnú vzorku produktu, musíme z košíka odstrániť všetky bežné produkty. Ste si istí, že chcete pokračovať